HGM-MZ Refrigerant Monitor System

Previous 8 / 10 Next

HGM-MZ Refrigerant Monitor System Refrigerant Monitoring System Bacharach (USA) Fixed Gas Detector HGM-MZ Refrigerant Monitor System Refrigerant Monitoring System Bacharach (USA) Fixed Gas Detector HGM-MZ Refrigerant Monitor System Refrigerant Monitoring System Bacharach (USA) Fixed Gas Detector


Multi-Zone Gas Leak Monitor
  • Monitors up to 16 remote areas, expandable to 48 points
  • Proprietary Infrared (NDIR) sensing technology
  • Low detection limits (as low as 1 ppm)
  • Long sampling distances (up to 1,200 ft / 365 m)
  • On-board visual/audible alarms, 4 relay contacts mitigates refrigerant loss

Description

Bacharach's Multi-Zone gas monitor offers superior performance, flexibility and functionality for low level continuous monitoring of refrigerants, carbon dioxide and ammonia. The 10 inch / 250 mm infrared sensor enables the Multi-Zone to accurately measure lowest ppm levels. A built-in library of over 50 gases and the scalability of the number of zones facilitate customization of the system. The large graphic LCD display and status LEDs provide a system-wide overview at one glimpse.

The Multi-Zone is a robust leak detector that offers effective refrigerant management. The sooner a loss of refrigerant is detected, the earlier countermeasures can be initiated, resulting in smaller recharge quantities of refrigerants. With the on-board relays and the optional Remote Display, the Multi-Zone fulfills the regulatory requirements as a refrigerant detection system. Using the Modbus interface or analog output, the monitor can be integrated into any BMS/BAS system.
 

Specifications

Type

4 to 16 point sampling system using IR sensor technology

Gases


 

Refrigerants:

CFCs, HFCs, HCFCs, HFOs

Natural Refrigerants:

Ammonia, Carbon Dioxide

Measuring Range *

Refrigerants 0 to 10,000 ppm
Ammonia 25 to 10,000 ppm
Carbon Dioxide 300 to 8,000 ppm

Sensitivity *

Refrigerants 1 ppm
Ammonia 25 ppm
Carbon Dioxide 10 ppm

Sampling Distance

0 to 1,200 ft. (0 to 365 m) for each sampling point

Display

Backlit, graphic LCD 160 x 128 pixel; three status LEDs

Output

Digital

Modbus® RTU via RS 485

Analog

4 to 20 mA (optional)

Power Supply

100 to 240 VAC, 50 / 60 Hz

Relay

3 alarm relays, 1 fault relay, SPDT

 

Rating 5 A @ 250 VAC, resistive load

Ambient Conditions



 

Temperature

32 to +122 °F (0 to +50 °C)

Humidity

5 to 90 %RH, non condensing

Altitude

0 to 6,560 ft (2,000 m)

Enclosure

Powder-coated aluminum

Size (w x h x d)

Approx. 13.7” x 12.3” x 5” (350 x 315 x 130 mm)

Weight

Approx. 15 lbs. (6.8 kg)

Approvals

CE, UL, CSA, EN 61010-1, EN 61326, EN 14624

* See data sheet for details